SKU : -
BUILT-IN ISOLATED TRANSFORMER INPUT -Nominal Voltage : 3 x 380VAC/400VAC/415VAC (3Ph + N or 3Ph + N + G) - Acceptable Voltage Range : 304VAC ~ 456VAC - Frequency : 50 Hz ±5 Hz( ± 10%) INVERTER - Nominal Voltage : 3 x 380VAC/400VAC/415VAC (Selectable) - Connection Type : Hardwire 5-wire (3Ph+N+G) - Waveform : Pure Sinewave - Output Voltage Stability : Steady state : ±1% ; Transient state : ±5% - Frequency : 50 Hz - Frequency Stability : ±1% - Frequency Synchronisation Speed : ±5 Hz (Equal to bypass working range) - Frequency Synchronisation Speed : 1 - 2 Hz/s - Power Factor : 0.8 - Crest Factor : 3 : 1 - Total Harmonic Distortion (THDv) : <2% (Linear Load) ; <4% (Non Linear Load)" BYPASS - Connection Type : Hardwire 5-wire (3Ph+N+G) - Input Voltage Range : 220 VAC ± 25% - Overload Capability : 1.5 In - 1.8 In 1h - 30s - Short-circuit Capability : 1.8 In - > 2.0 In 30s - 200ms